Characteristics
Construction
Type :
multicore cable
Core :
flexible bare copper - class 5 as per IEC 60228
Insulation :
isovinyl
Shape :
flat or round cable
Sheath :
Profiprene
Colour of outer cable sheath :
blue RAL 5012
Production
Standard :
3x16 au 3x70 / 4G1.5 au 4x70 mm²
Options :
please consult our data sheet FT 2004
Application
General use :
ideal for the power supply of deep submersible pumps
Approvals - Standards
Flame retardant :
IEC 60332-1-2 / EN 60332-1-2 /NF C 32-070 test C2
Bureau VERITAS :
AD8 as per NF C 32-102-16 A-B
General characteristics
Operating environment :
resistance to salt mists
Resistance to water :
permanent immersion AD8, depth of immersion 450 m - 45 bars
Thermal characteristics
Continuous operating temperature :
-40°C to +70°C (outdoor fixed installation), -25°C to +70°C (outdoor flexible installation), +60°C (underwater fixed installation: )
Electrical characteristics
OperatingVoltage :
600 / 1000V (fixed installation), 450 / 750V (flexible installation)
Test voltage :
2500 V