Characteristics
Construction
Type :
shielded twisted pair cable
Core :
rigid bare copper
Insulation :
polyethylene
Electrical screen :
aluminium/PET tape, continuity wire
Other :
cross filler
Sheath :
halogen free thermoplastic
Colour of insulated wire(s) :
please consult our data sheet for further information
Colour of outer cable sheath :
brown
Production
Standard :
1, 2, 3 or 5 pairs
Options :
please consult our data sheet FT 6091
Application
Construction and infrastructure :
Halogen-free cable with low smoke emission for wiring fire safety and detection devices
Approvals - Standards
CPR cable class :
EN 50575
Construction :
UTE C 93-529-2
Flame retardant :
Resistance to vertical flame propagation on insulated cables according to IEC 60332-1-2
Improved fire performance: Euroclass Cca-s2,d2,a2
Improved fire performance: Euroclass Cca-s2,d2,a2
Halogen free :
EN 60754-1 / EN 60754-2
Low toxicity :
IEC 60754-2 / EN 60754-2
Low smoke :
EN 61034-2
General characteristics
Data transmission :
maximum mutual capacitance 55 pF/m, maximum attenuation at 2 MHz: 3.5 dB/m
Thermal characteristics
Continuous operating temperature :
-20°C to +70°C
Electrical characteristics
Impedance :
100 ohms +/- 20 ohms