Characteristics
Construction
Type :
electrical wire
Core :
nickel-plated copper
Insulation :
two heat-sealed crossed polyimide tapes
Production
Standard :
0.14 to 50 mm²
Options :
please consult our data sheet FT 3119
Application
High-risk sites :
all cabling requiring enhanced chemical resistance and resistance to radiations (chemical, nuclear industry, etc.)
Heating elements :
cabling for heating resistors, cartridges, bands and plates
Approvals - Standards
Others :
nickel-plated copper complying with the 2% class as per standard ASTM B355
General characteristics
Chemical behaviour :
good resistance to moisture and common chemical agents
Radiation resistance :
excellent resistance of polyimide material: 1.109 rad
Thermal characteristics
Continuous operating temperature :
-190°C to +250°C
Electrical characteristics
OperatingVoltage :
300 / 500V
Test voltage :
2000 V