Skip to main content
ENERSYL ZH INSTRUM

ENERSYL®
ZH INSTRUM

FT6104

Characteristics

Construction
Type : multi-pair cable
Core : flexible bare copper - class 5 as per IEC 60228
Insulation : cross-linked halogen free polyolefine
Electrical screen : general metallic tape and/or braid (optional: individual)
Shielding : optional: please consult our data sheet
Armour : optional: please consult our data sheet
Sheath : HFFR - type ST8 as per IEC 60502-1
Colour of outer cable sheath : green
Production
Standard : 1 to 37 pairs, triples or quads, 0.5 / 0.9 / 1.5 mm²
Options : please consult our data sheet FT 6104
Application
High-risk sites : cables for power stations, high risk sites or nuclear plants
General characteristics
Weather conditions : resistance to UV ≥ 2000 hours as per EN 1647
Chemical behaviour : good resistance to acid and base, excellent resistance to aliphatic hydrocarbons
Resistance to water : type AD7 as per IEC 60529 without immersion of ends
Further thermal information : maximum core temperature +90°C
Thermal characteristics
Continuous operating temperature : -30°C to +80°C
Electrical characteristics
OperatingVoltage : 300 / 500V
Test voltage : 2000 V
Approvals - Standards
Flame retardant, test on bunched cables : IEC 60332-3-24 / EN 60332-3-24
Flame retardant : IEC 60332-1-2 / EN 60332-1-2 /NF C 32-070 test C2
Halogen free : IEC 60754-1 / EN 60754-1
Low toxicity : IEC 60754-2 / EN 60754-2
Low smoke : IEC 61034-2 / EN 61034-2
A question, an information?
Contact our team
Contact us
Contactez-nous