Characteristics
Construction
Type :
thermocouple cable
Couple(s) :
JX, TX, KX, EX, BC, KCB
Insulation :
cross-linked halogen free polyolefine
Electrical screen :
optional: please consult our data sheet for further information
Shielding :
optional: please consult our data sheet
Armour :
optional: please consult our data sheet
Sheath :
HFFR - type ST8 as per IEC 60502-1
Category :
extension cable - tolerance class: 1, compensation cable - tolerance class: 2
Colour of outer cable sheath :
IEC
Production
Standard :
1 to 37 pairs, 0.5 / 1 mm²
Options :
please consult our data sheet FT 6105
Approvals - Standards
Flame retardant, test on bunched cables :
IEC 60332-3-24 / EN 60332-3-24
Flame retardant :
IEC 60332-1-2 / EN 60332-1-2 /NF C 32-070 test C2
Halogen free :
IEC 60754-1 / EN 60754-1
Low toxicity :
IEC 60754-2 / EN 60754-2
Low smoke :
IEC 61034-2 / EN 61034-2
Temperature measurement :
IEC 60584-1, IEC 60584-2, IEC 60584-3
General characteristics
Weather conditions :
resistance to UV ≥ 2000 hours as per EN 1647
Chemical behaviour :
good resistance to acid and base, excellent resistance to aliphatic hydrocarbons
Resistance to water :
type AD7 as per IEC 60529 without immersion of ends
Thermal characteristics
Continuous operating temperature :
-30°C to +80°C
Electrical characteristics
Test voltage :
500V